Single-module Residual Current B Type RCBO
The EKL19-40B is a compact Type B residual current device for modern electrical systems. It supports 230/240 V and up to 40 A. It offers protection against overcurrent, short circuit, and fault currents and features advanced DC residual current detection—ideal for charging stations, photovoltaic systems, and heat pumps. With a rated breaking capacity of 6 kA, bidirectional operation, and compliance with IEC/EN standards, it guarantees reliable performance.
Standard: IEC61009-1, IEC62423
Residual Current Type: B
Rated current: 16, 20, 25, 32, 40A
Rated voltage: 230/240~
Number of poles: 2P(1P+N)
Rated Residual Operating Current (IAn): 30mA
Rated short-circuit breaking capacity: 6kA
Tripping curve: B, C
Ambient air temperature: -25...+55 ºC
Storage temperature: -25...+70 ºC
Incoming method: Bi-directional
Certificates: CE, UKCA
The EKL19-40B is a compact Type B residual current device for modern electrical systems. It supports 230/240 V and up to 40 A. It offers protection against overcurrent, short circuit, and fault currents and features advanced DC residual current detection—ideal for charging stations, photovoltaic systems, and heat pumps. With a rated breaking capacity of 6 kA, bidirectional operation, and compliance with IEC/EN standards, it guarantees reliable performance.
Standard: IEC61009-1, IEC62423
Residual Current Type: B
Rated current: 16, 20, 25, 32, 40A
Rated voltage: 230/240~
Number of poles: 2P(1P+N)
Rated Residual Operating Current (IAn): 30mA
Rated short-circuit breaking capacity: 6kA
Tripping curve: B, C
Ambient air temperature: -25...+55 ºC
Storage temperature: -25...+70 ºC
Incoming method: Bi-directional
Certificates: CE, UKCA
Product selection form
Parâmetro | Valor |
---|---|
Standard | IEC/EN 61009-1, IEC/EN 62423 |
Protection | Ground fault, Overcurrent and short circuit |
Type of trip | Groundfault: Electronic; Overload and short circuit: Thermo-magnetic |
Residual current type | B: residual AC, pulsating and smooth DC current, high frequency (≤1kHz) |
No. of poles | 1P+N (18mm, with switched neutral) |
Insulation voltage (Ui) | 500V |
Rated voltage (Ue) | 230/240V~ |
Rated currents (In) | 6,8,10,13,16,20,25,32,40A |
Rated sensitivity currents (IΔn) | 30mA |
Residual current off time under (IΔn) | ≤0.1s |
Rated residual making and breaking capacity (IΔm) | 500A (In≤50A) |
Rated frequency | 50/60Hz |
Rated short-circuit capacity (Icn) | 6kA |
Energy limiting class | 3 |
Rated impulse withstand voltage (Uimp (1.2/50μs) | 4kV |
Dielectric test voltage | 960±15°C (Enclosure), 650±10°C (Handle) |
Thermal tripping characteristics | 1.13In: No tripping within an hour; 1.45In: Tripping within an hour |
Instantaneous tripping characteristics | B: 3In-5In; C: 5In-10In |
Electrical life | 4,000 Cycles |
Mechanical life | 10,000 Cycles |
Contact position indication | green OFF / red ON |
Protection degree | IP20 |
Ambient temperature | -25°C ~ +55°C |
Storage temperature | -30°C ~ +70°C |
Terminal connection type | Cable / Pin-type busbar |
Max. terminal size for cable | 16mm² |
Max. tightening torque | 2.0 N.m |
Installation | Mounting on 35mm DIN rail |
Incoming method | Bi-directional |
Schaltbild