RCBO 6kA Magnetic Type Residual Current Operated Circuit Breaker
The EKL3-40M 6kA electromagnetic residual current device (RCBO) with overcurrent protection, developed by ETEK Electric, is a state-of-the-art protection device. It combines residual current and overcurrent protection in a single device, reliably protecting circuits from ground fault currents, overloads, and short circuits. With a robust breaking capacity of 6kA, this RCBO is ideal for demanding industrial and commercial applications where reliability and safety are paramount.
Technical data:
- Standard: IEC61009-1
- Type: AC, A
- Rated current: 6–40 A
- Rated voltage: 230/240 V~
- Number of poles: 2P (1P+N)
- Rated residual current (IΔn): 30, 100, 300 mA
- Rated breaking capacity: 6 kA
- Trigger characteristics: B, C
- Ambient temperature: -25…+55 ºC
- Connection: Top and bottom
- Certificates: CE, CB, UKCA, S
The EKL3-40M 6kA electromagnetic residual current device (RCBO) with overcurrent protection, developed by ETEK Electric, is a state-of-the-art protection device. It combines residual current and overcurrent protection in a single device, reliably protecting circuits from ground fault currents, overloads, and short circuits. With a robust breaking capacity of 6kA, this RCBO is ideal for demanding industrial and commercial applications where reliability and safety are paramount.
Technical data:
- Standard: IEC61009-1
- Type: AC, A
- Rated current: 6–40 A
- Rated voltage: 230/240 V~
- Number of poles: 2P (1P+N)
- Rated residual current (IΔn): 30, 100, 300 mA
- Rated breaking capacity: 6 kA
- Trigger characteristics: B, C
- Ambient temperature: -25…+55 ºC
- Connection: Top and bottom
- Certificates: CE, CB, UKCA, S
Technical data
Parameter | Value |
---|---|
Standard | IEC/EN61009-1 |
Protection | Ground fault, Overcurrent and short circuit, Over voltage (selectable) |
Type of trip | Ground fault: Electro-magnetic Overload and short circuit: Thermo-magnetic |
Type of protection (electric leakage) | AC, A |
No. of poles | 1P+N 2 module, N line with disconnected |
Rated current (In) | 6, 10, 16, 20, 25, 32, 40A |
Rated voltage (Ue) | 230/240V~ |
Rated frequency | 50/60Hz |
Rated sensitivity currents (I△n) | 30, 100, 300mA |
Residual current off-time under I△n | ≤ 0.1s |
Rated residual making and breaking capacity (I△m) | 500A (In≤50A) |
Rated breaking capacity | 6,000A |
Energy limiting class | 3 |
Rated impulse withstand voltage (1.2/50) Uimp | 4,000V |
Dielectric test voltage at ind. Freq. for 1 min | 2kV |
Thermal release characteristic | (1.13–1.45) x In |
Magnetic release characteristic | B: (3–5) x In, C: (5–10) x In |
Electrical life | 4,000 Cycles |
Mechanical life | 10,000 Cycles |
Contact position indicator | Yes |
Ground fault indicator | Yes |
Protection degree | IP20 |
Ambient temperature | -25℃ to +55℃, Max. 95% humidity |
Terminal connection type | Cable / Pin-type busbar / Fork-type busbar |
Max. terminal size for cable | 25mm² |
Max. tightening torque | 2.5N·m |
Installation | Mounting on 35mm DIN rail |
Connection | From top and bottom |
Schaltbild

Installationsgröße

Product selection form
B Curve – Type A
Poles | Rated Current (A) | Sensitivity | ||
---|---|---|---|---|
30mA | 100mA | 300mA | ||
1P+N | 6A | EKL3-40M-1NB0630 | EKL3-40M-1NB06100 | EKL3-40M-1NB06300 |
1P+N | 8A | EKL3-40M-1NB0830 | EKL3-40M-1NB08100 | EKL3-40M-1NB08300 |
1P+N | 10A | EKL3-40M-1NB1030 | EKL3-40M-1NB10100 | EKL3-40M-1NB10300 |
1P+N | 13A | EKL3-40M-1NB1330 | EKL3-40M-1NB13100 | EKL3-40M-1NB13300 |
1P+N | 16A | EKL3-40M-1NB1630 | EKL3-40M-1NB16100 | EKL3-40M-1NB16300 |
1P+N | 20A | EKL3-40M-1NB2030 | EKL3-40M-1NB20100 | EKL3-40M-1NB20300 |
1P+N | 25A | EKL3-40M-1NB2530 | EKL3-40M-1NB25100 | EKL3-40M-1NB25300 |
1P+N | 32A | EKL3-40M-1NB3230 | EKL3-40M-1NB32100 | EKL3-40M-1NB32300 |
1P+N | 40A | EKL3-40M-1NB4030 | EKL3-40M-1NB40100 | EKL3-40M-1NB40300 |
C Curve – Type A
Poles | Rated Current (A) | Sensitivity | ||
---|---|---|---|---|
30mA | 100mA | 300mA | ||
1P+N | 6A | EKL3-40M-1NC0630 | EKL3-40M-1NC06100 | EKL3-40M-1NC06300 |
1P+N | 8A | EKL3-40M-1NC0830 | EKL3-40M-1NC08100 | EKL3-40M-1NC08300 |
1P+N | 10A | EKL3-40M-1NC1030 | EKL3-40M-1NC10100 | EKL3-40M-1NC10300 |
1P+N | 13A | EKL3-40M-1NC1330 | EKL3-40M-1NC13100 | EKL3-40M-1NC13300 |
1P+N | 16A | EKL3-40M-1NC1630 | EKL3-40M-1NC16100 | EKL3-40M-1NC16300 |
1P+N | 20A | EKL3-40M-1NC2030 | EKL3-40M-1NC20100 | EKL3-40M-1NC20300 |
1P+N | 25A | EKL3-40M-1NC2530 | EKL3-40M-1NC25100 | EKL3-40M-1NC25300 |
1P+N | 32A | EKL3-40M-1NC3230 | EKL3-40M-1NC32100 | EKL3-40M-1NC32300 |
1P+N | 40A | EKL3-40M-1NC4030 | EKL3-40M-1NC40100 | EKL3-40M-1NC40300 |