AFDD RCBO With Arc Fault Protective
EKL17-40AFD: Compact protection device with arc detection
The EKL17-40AFD devices are single-module circuit breakers that can be integrated into existing busbar systems. They offer comprehensive protection in a single device – against overcurrent, short circuit, residual current, and series and parallel arcing. Available with B and C characteristics, they are ideal as a direct replacement for existing RCBOs in consumer units.
- Standards: IEC61009-1, IEC62026
 - Protection functions: Serial and parallel arc detection, combined arc, short-circuit, overload and fault current detection
 - RCBO type: AC, A
 - Rated current: 6–40 A
 - Rated voltage: 230/240 V~
 - Number of poles: 1P+N (with switched neutral conductor)
 - Rated residual current (IΔn): 10, 30, 100, 300 mA
 - Rated breaking capacity: 6 kA
 - Trigger characteristics: B, C
 - Ambient temperature: -25…+40 ºC
 - Connection: From below
 - Certificates: CE, CB
 
EKL17-40AFD: Compact protection device with arc detection
The EKL17-40AFD devices are single-module circuit breakers that can be integrated into existing busbar systems. They offer comprehensive protection in a single device – against overcurrent, short circuit, residual current, and series and parallel arcing. Available with B and C characteristics, they are ideal as a direct replacement for existing RCBOs in consumer units.
- Standards: IEC61009-1, IEC62026
 - Protection functions: Serial and parallel arc detection, combined arc, short-circuit, overload and fault current detection
 - RCBO type: AC, A
 - Rated current: 6–40 A
 - Rated voltage: 230/240 V~
 - Number of poles: 1P+N (with switched neutral conductor)
 - Rated residual current (IΔn): 10, 30, 100, 300 mA
 - Rated breaking capacity: 6 kA
 - Trigger characteristics: B, C
 - Ambient temperature: -25…+40 ºC
 - Connection: From below
 - Certificates: CE, CB
 
Technical data
Complete Circuit Protection
| Dispositivo | Over Current | Short Circuit | Earth Leakage | Series Arc Fault | Parallel Arc Fault | 
|---|---|---|---|---|---|
| MCB | √ | √ | × | × | × | 
| RCCB | × | × | √ | × | × | 
| RCBO | √ | √ | √ | × | × | 
| AFDD | × | × | × | √ | √ | 
| AFDD Integrated with RCBO | √ | √ | √ | √ | √ | 
Limit values of operating criteria for AFDD at low arc currents up to 63 A (IEC62026)
Limit values of break time for Ue 230V AFDD
| Test arc current (r.m.s. values) | Max breaking time | 
|---|---|
| 2.5A | 1s | 
| 5A | 0.5s | 
| 10A | 0.25s | 
| 16A | 0.15s | 
| 32A | 0.12s | 
| 63A | 0.12s | 
Note:
- The test arc current is the expected current before ignition occurs in the test circuit.
 - Low arc currents can occur due to insulation faults phase to earth or series arcing.
 
Schaltbild
  Installationsgröße
  Technical data
| Auslöseart | Fehlerstrom: Elektronisch Überlast und Kurzschluss: Thermisch-magnetisch  | 
| Art des Fehlerstromschutzes | A | 
| Anzahl der Pole | 1P+N (N-Leiter schaltbar) | 
| Nennstrom (In) | 6, 10, 16, 20, 25, 32, 40A | 
| Nennfehlerströme (IΔn) | 10, 30, 100, 300mA | 
| Auslösezeit bei IΔn | ≤ 0,1 s | 
| Bemessungsausschaltvermögen (IΔm) | 500A | 
| Nennspannung (Ue) | 230/240V | 
| Nennfrequenz | 50/60Hz | 
| Bemessungsschaltvermögen | 6.000A | 
| Energiebegrenzungsklasse | 3 | 
| Stoßspannungsfestigkeit (1,5/50) Uimp | 4.000V | 
| Isolationsprüfspannung bei 50Hz für 1 Min. | 2kV | 
| Thermische Auslösekennlinie | (1,13–1,45) × In | 
| Magnetische Auslösekennlinie | B: (3–5) × In, C: (5–10) × In | 
| Elektrische Lebensdauer | 4.000 Schaltspiele | 
| Mechanische Lebensdauer | 10.000 Schaltspiele | 
| Schaltstellungsanzeige | Ja | 
| Schutzart | IP20 | 
| Umgebungstemperatur | -25℃ bis +40℃, max. 95% Luftfeuchtigkeit | 
| Anschlussart | Kabel-/Stiftsammelschiene | 
| Max. Leiterquerschnitt | L (Eingang): 25mm², N/L (Ausgang): 16mm² | 
| Max. Anzugsdrehmoment | L (Eingang): 2,5Nm, N/L (Ausgang): 2Nm | 
| Montage | Montage auf 35mm DIN-Schiene | 
| Anschlussrichtung | Von unten | 
Product selection form – AFDD/RCBO EK17-40AFD
B Curve
| Rated Current (A) | 10mA | 30mA | 100mA | 300mA | 
|---|---|---|---|---|
| 6A | EKL17-40AFD-1NB0610A | EKL17-40AFD-1NB0630A | EKL17-40AFD-1NB06100A | EKL17-40AFD-1NB06300A | 
| 10A | EKL17-40AFD-1NB1010A | EKL17-40AFD-1NB1030A | EKL17-40AFD-1NB10100A | EKL17-40AFD-1NB10300A | 
| 16A | EKL17-40AFD-1NB1610A | EKL17-40AFD-1NB1630A | EKL17-40AFD-1NB16100A | EKL17-40AFD-1NB16300A | 
| 20A | EKL17-40AFD-1NB2010A | EKL17-40AFD-1NB2030A | EKL17-40AFD-1NB20100A | EKL17-40AFD-1NB20300A | 
| 25A | EKL17-40AFD-1NB2510A | EKL17-40AFD-1NB2530A | EKL17-40AFD-1NB25100A | EKL17-40AFD-1NB25300A | 
| 32A | EKL17-40AFD-1NB3210A | EKL17-40AFD-1NB3230A | EKL17-40AFD-1NB32100A | EKL17-40AFD-1NB32300A | 
| 40A | EKL17-40AFD-1NB4010A | EKL17-40AFD-1NB4030A | EKL17-40AFD-1NB40100A | EKL17-40AFD-1NB40300A | 
C Curve
| Rated Current (A) | 10mA | 30mA | 100mA | 300mA | 
|---|---|---|---|---|
| 6A | EKL17-40AFD-1NC0610A | EKL17-40AFD-1NC0630A | EKL17-40AFD-1NC06100A | EKL17-40AFD-1NC06300A | 
| 10A | EKL17-40AFD-1NC1010A | EKL17-40AFD-1NC1030A | EKL17-40AFD-1NC10100A | EKL17-40AFD-1NC10300A | 
| 16A | EKL17-40AFD-1NC1610A | EKL17-40AFD-1NC1630A | EKL17-40AFD-1NC16100A | EKL17-40AFD-1NC16300A | 
| 20A | EKL17-40AFD-1NC2010A | EKL17-40AFD-1NC2030A | EKL17-40AFD-1NC20100A | EKL17-40AFD-1NC20300A | 
| 25A | EKL17-40AFD-1NC2510A | EKL17-40AFD-1NC2530A | EKL17-40AFD-1NC25100A | EKL17-40AFD-1NC25300A | 
| 32A | EKL17-40AFD-1NC3210A | EKL17-40AFD-1NC3230A | EKL17-40AFD-1NC32100A | EKL17-40AFD-1NC32300A | 
| 40A | EKL17-40AFD-1NC4010A | EKL17-40AFD-1NC4030A | EKL17-40AFD-1NC40100A | EKL17-40AFD-1NC40300A |