RCBO 3P+N Residual Current Circuit Breaker with Overcurrent Protection
EKL37-40: Compact 3P+N RCBO from ETEK Electric
The EKL37-40 from ETEK Electric is a 40 A 3P+N RCBO that offers comprehensive protection in a space-saving enclosure measuring just 54 mm wide. This versatile device combines the functions of a residual current device (RCD) and a miniature circuit breaker (MCB) in a single unit—ideal for protecting three-phase systems with a neutral conductor.
- Standard: IEC61009-1
- Type: AC, A
- Rated current: 6–40 A
- Rated voltage: 400/415 V~
- Number of poles: 3P+N, 54 mm width
- Rated residual current (IΔn): 10, 30, 100, 300 mA
- Rated breaking capacity: 6 kA, 10 kA
- Trigger characteristics: B, C
- Ambient temperature: -25…+40 ºC
- Connection: From below
EKL37-40: Compact 3P+N RCBO from ETEK Electric
The EKL37-40 from ETEK Electric is a 40 A 3P+N RCBO that offers comprehensive protection in a space-saving enclosure measuring just 54 mm wide. This versatile device combines the functions of a residual current device (RCD) and a miniature circuit breaker (MCB) in a single unit—ideal for protecting three-phase systems with a neutral conductor.
- Standard: IEC61009-1
- Type: AC, A
- Rated current: 6–40 A
- Rated voltage: 400/415 V~
- Number of poles: 3P+N, 54 mm width
- Rated residual current (IΔn): 10, 30, 100, 300 mA
- Rated breaking capacity: 6 kA, 10 kA
- Trigger characteristics: B, C
- Ambient temperature: -25…+40 ºC
- Connection: From below
Technical data
Parameter | Wert (Deutsch) |
---|---|
Norm | IEC/EN 61009-1 |
Schutzfunktion | Fehlerstrom, Überstrom und Kurzschluss |
Auslöseart | Fehlerstrom: Elektronisch Überlast und Kurzschluss: Thermomagnetisch |
Polzahl | 3P+N, kompakt, 3 Module (54 mm Breite) |
Schutzart | AC, A |
Nennstrom (In) | 6, 10, 16, 20, 25, 32, 40A |
Bemessungsauslösestrom IΔn | 10, 30, 100, 300mA |
Ausschaltzeit unter IΔn | ≤0,1s |
Bemessungs-Schaltvermögen IΔm | 500A (In ≤ 50A) |
Betriebsspannung (Ue) | 400/415V~ |
Nennfrequenz | 50/60Hz |
Kurzschluss-Schaltvermögen | EKL37-40: 6kA, EKL37-40H: 10kA |
Energiebegrenzungsklasse | 3 |
Stoßspannungsfestigkeit (1.2/50) Uimp | 4.000V |
Isolationsprüfspannung 1 min | 2kV |
Thermische Auslösung | (1,13–1,45) × In |
Magnetische Auslösung | B: (3–5) × In, C: (5–10) × In |
Elektrische Lebensdauer | 4.000 Zyklen |
Mechanische Lebensdauer | 10.000 Zyklen |
Schaltstellungsanzeige | Ja |
Schutzart (IP) | IP20 |
Umgebungstemperatur | -25℃ bis +40℃, max. 95% Luftfeuchtigkeit |
Anschlussart | Kabel-/Stift-/Gabelschiene |
Max. Leiterquerschnitt | 16mm² |
Max. Anzugsmoment | 2,5 Nm |
Montage | Montage auf 35 mm DIN-Schiene |
Anschlussrichtung | Von unten |
Schaltbild

Installationsgröße