1P+N Residual Current Circuit Breaker with Overcurrent Protection (RCBO)
The EKL17-40 is an advanced residual current device (RCD) with overcurrent protection (RCBO) developed by ETEK China. This innovative device combines the functions of a residual current device (RCD) and a miniature circuit breaker (MCB) into a single, efficient unit – providing reliable protection against fault currents, overloads, and short circuits.
- Standard: IEC61009-1
- Type: AC, A
- Rated current: 6–40 A
- Rated voltage: 230/240 V~
- Number of poles: 1-pole
- Rated residual current (IΔn): 10, 30, 100, 300 mA
- Rated breaking capacity: 6 kA
- Trigger characteristics: B, C
- Ambient temperature: -25…+40 ºC
- Connection: From below
- Certificates: CE, CB
The EKL17-40 is an advanced residual current device (RCD) with overcurrent protection (RCBO) developed by ETEK China. This innovative device combines the functions of a residual current device (RCD) and a miniature circuit breaker (MCB) into a single, efficient unit – providing reliable protection against fault currents, overloads, and short circuits.
- Standard: IEC61009-1
- Type: AC, A
- Rated current: 6–40 A
- Rated voltage: 230/240 V~
- Number of poles: 1-pole
- Rated residual current (IΔn): 10, 30, 100, 300 mA
- Rated breaking capacity: 6 kA
- Trigger characteristics: B, C
- Ambient temperature: -25…+40 ºC
- Connection: From below
- Certificates: CE, CB
Technical data
Technical Data
Parameter | Value |
---|---|
Standard | IEC/EN61009-1 |
Protection | Ground fault, Overcurrent and short circuit, Over-voltage (selectable) |
Type of trip | Ground fault: Electronic Overload and short circuit: Thermo-magnetic |
Type of protection (electric leakage) | AC, A |
No. of poles | 1P+N 1 module, N line with disconnected |
Rated currents (In) | 6, 10, 16, 20, 25, 32, 40A |
Rated sensitivity currents I△n | 10, 30, 100, 300mA |
Residual current off-time under I△n | ≤ 0.1s |
Rated residual making and breaking capacity (I△m) | 500A (In≤50A) |
Rated voltage (Ue) | 230/240V~ |
Rated frequency | 50/60Hz |
Rated breaking capacity | 6,000A |
Energy Limiting Class | 3 |
Rated impulse withstand voltage (1.2/50) Uimp | 4,000V |
Dielectric test voltage at Ind. Freq. for 1 min | 2kV |
Thermal release characteristic | (1.13–1.45) x In |
Magnetic release characteristic | B: (3–5) x In, C: (5–10) x In |
Electrical life | 4,000 Cycles |
Mechanical life | 10,000 Cycles |
Contact position indicator | Yes |
Protection degree | IP20 |
Ambient temperature | -25℃ to +40℃, Max. 95% humidity |
Terminal connection type | Cable/Pin-type busbar |
Max. terminal size for cable | L(in): 25mm², N/L(out): 16mm² |
Max. tightening torque | L(in): 2.5N·m, N/L(out): 2N·m |
Installation | Mounting on 35mm DIN rail |
Connection | From bottom |
Schaltbild